33 ALARM BELL TIMEOUT 1
0 = No timeout
1 = 4 min
2 = 8 min
3 = 12 min
4 = 16 min
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min (option 1)
NOTE: If the fire sounder of
32 is programmed for no timeout with
33 programmed for 4 to 16 minutes of alarm bell ringing, and a
burglary alarm is triggered at the same time a fire is detected, the
alarm bell will timeout as specified in
33.
34 EXIT DELAY 9 | 9
00 - 99 = exit delay time in seconds
The system will wait the time entered before sounding an alarm if the
exit door is left opened after the system has been armed.
35 ENTRY DELAY 1 6| 0
00 - 99 = entry delay time in secs.
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 20 seconds
36 ENTRY DELAY 2 9| 0
00 - 99 = entry delay time in secs.
The system will wait the time entered before sounding alarm upon
entering.
UL installations: must be set for a maximum of 20 seconds
37 AUDIBLE EXIT WARNING 1
0 = no exit warning sound
1 = provide exit warning sound when armed AWAY
Warning sound consists of slow continuous beeps until last 5 seconds,
when it changes to fast beeps. The warning sound will end at the
termination of Exit time.
38 CONFIRMATION OF ARMING DING 0
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from RF button or RF keypad only
(ding occurs when the system receives the RF transmission.)
Confirmation of arming is 1/2 second external sounder “ding” when
closing report is sent, or at the end of exit delay.
39 POWER UP IN PREVIOUS STATE 1
0 = always power up in a disarmed state
1 = assume the system status prior to power down
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted.
Note that if the previous state was armed AWAY or HOME, the
system will not respond to sensor changes for 1 minute, which allows
time for sensors such as PIRs to stabilize. This means that if a zone
faults during that 1 minute time period, the system will not detect the
faulting and would power up into the armed ON AWAY or ON HOME
original state.
UL installations: must be 1 (power up in previous state)